Parameter | СО2-1 | Measurement unit |
---|---|---|
Power supply/ power consumption ![]() |
24 VAC (50/60 Hz ± 10%), 24 VDC/1.6 W Max | W |
Gas detection analyzer ![]() |
Non-dispersive infrared detector (NDIR) with self-calibration system | – |
CO2 detection range ![]() |
0–2,000 ppm (parts per million) | – |
Accuracy at 25°С (77°F), 2000 ppm ![]() |
±30 ppm + 3 % of reading | – |
Response time ![]() |
max. 2 min | – |
Warm up time for each turning-on ![]() |
2 hours (first time), 2 minutes (operation) | – |
Analogue output ![]() |
0-10 VDC (factory setting), 4-20 mA (selectable by jumpers) | – |
On/Off output ![]() |
1X2A switch load. Four set points selectable by jumpers | – |
6 LED lights – CO2 indicators ![]() |
– | |
Operating conditions/ storage recommendations ![]() |
– | |
Net weight/ Dimensions ![]() |
kg | |
Mounting | outdoor mounting | – |