Description
Technical specifications
AIR FLOW – SOUND PRESSURE ROOM (Lp10A) *)
GTH | l/s | ||
Size | 25 dB(A) | 30 dB(A) | 35 dB(A) |
200-100 | 28 | 44 | 50 |
300-100 | 42 | 48 | 78 |
400-100 | 40 | 52 | 90 |
500-100 | 65 | 78 | 125 |
300-150 | 60 | 70 | 130 |
400-150 | 95 | 115 | 150 |
500-150 | 93 | 110 | 155 |
400-200 | 98 | 120 | 180 |
500-200 | 145 | 170 | 250 |
600-200 | 145 | 225 | 350 |
Data in the table applies to supply air for the combination GTH + TRG at a total pressure drop of 50 Pa.
*) Lp10A = Sound pressure incl. A-filter with 4 dB room attenuation and 10 m2 room absorption area.